Delivery And Installation Of The Ventilation Systems For A Vehicle Hall And The Associated Adjoining Rooms.Delivery And Assembly Of The Ventilation Systems For A Vehicle Hall And The Associated Adjoining Rooms. Essential Services:- A Central Supply And Exhaust Air Device For Roof Installation With Heat Recovery, 4,200 M³/H Supply And Exhaust Air Each. - A Separate Side Room Ventilation With Two Ec Fans For Supply And Exhaust Air, Each 190 M³/H, Including Filter Box. - Two Hot Water Heaters With 9.9 Kw And 2.1 Kw Heating Output. - Approx. 134 M² Of Rectangular Air Ducts Including Fittings And Approx. 8.3 M Of Spiral Folded Pipe Dn 125 To Dn 355 Plus Fittings; Including Silencers, Flaps And Cleaning Accesses.- Four Motor-Adjustable Displacement Outlets, Four Exhaust Grilles, Four Air Valves And Two Weather Protection Grilles. - Approx. 24 M² Of Mineral Wool Insulation, 50 Mm, With Aluminum Sheet Metal Jacket And Approx. 4 M² Of Elastomer Insulation, 25 Mm. - Duct Elevations And Fastenings, Connections To On-Site Roof And Facade Ducts As Well As Mobile Crane And Assembly Scaffolding Services. - Testing, Commissioning, Air Volume Adjustment, Instruction And Inventory Documentation As Well As Separate Maintenance Services For Five Years.